Watlow Electric Silver Series Manual de usuario Pagina 2

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 6
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 1
Specifications
Line Voltage/Power
100 to 240VAC, +10/-15%; (85-264VAC), 50/60Hz, ±5%
24VAC/VDC, +10/-15%; 50/60Hz, ±5%
12VA max. power consumption without mechanical
contactor in system
50VA max. power consumption with mechanical
contactor used in system, 140VA if using external
contactor
Data retention upon power failure via nonvolatile memory
Environment
0 to 149°F (-18 to 70°C) operating temperature
-40 to 185°F (-40 to 85°C) storage temperature
0 to 90% RH, non-condensing
Accuracy
Calibration accuracy and sensor conformity: ±0.1%
of span, ±1°C @ the calibrated ambient temperature and
rated line voltage
Types R, S, B: 0.2%
Type T below -50°C: 0.2%
Calibration ambient temperature @ 77°F ±5°F (25°C ±3°C)
Accuracy span: 1000°F (540°C) min.
Temperature stability: ±0.1°F/°F (±0.1°C/°C) rise in
ambient max.
Agency Approvals
UL
®
, CSA, CE, IP65/NEMA 4X indoor use RUI, RoHS,
W.E.E.E.
Limit version features FM approval
Controller
Microprocessor based user-selectable control modes
PID module: single universal input, 2 outputs
Limit module: single universal input, 2 outputs
Two total additional digital input/outputs shared between
PID and limit functions
Control sampling rates: input = 10Hz, outputs = 10Hz
Isolated EIA 485 Modbus
®
RTU serial communications
Wiring Termination—Touch Safe Terminals
Input, power and controller output terminals touch safe
removable 12 to 22 AWG
Power load terminals 6 to 12 AWG
Tightening torque: 30 in.-lbs
Universal Input
Thermocouple, grounded or ungrounded sensors
>20M input impedance
Max. of 20 source resistance
RTD 2- or 3-wire, platinum, 100 and 1000 @ 0°C
calibration to DIN curve (0.00385//°C)
Process, 0-20mA @ 100, or 0-10VDC @ 20k input
impedance; scalable, 0-50mV
Inverse scaling
Digital Input
Update rate: 1Hz
Dry contact or dc voltage
DC voltage
Max. input: 36V at 3mA
Min. high state: 3V at 0.25mA
Max. low state: 2V
Dry contact
Max. short circuit: 13mA
Min. open resistance: 500
Max. closed resistance: 100
Current Measurement
Accuracy: typical ±1A, max. error ±3A
Accuracy and operating range: 0 to 75A
Digital Output
Update rate: 1Hz
Output voltage: 24V, current limit 10mA
Allowable Operating Range
Type J: 32 to 1500°F or 0 to 815°C
Type K: -328 to 2500°F or -200 to 1370°C
Type T: -328 to 750°F or -200 to 400°C
Type N: 32 to 2372°F or 0 to 1300°C
Type E: -328 to 1470°F or -200 to 800°C
Type C: 32 to 4200°F or 0 to 2315°C
Type D: 32 to 4200°F or 0 to 2315°C
Type F: 32 to 2543°F or 0 to 1395°C
Type R: 32 to 3200°F or 0 to 1760°C
Type S: 32 to 3200°F or 0 to 1760°C
Type B: 32 to 3300°F or 0 to 1816°C
RTD (DIN): -328 to 1472°F or -200 to 800°C
Process: -1999 to 9999 units
Output Hardware
User selectable for heat/cool as on-off, P, PI, PD, PID, or
alarm action. Not valid for limit controls
Electromechanical relay. Form A, rated 2A
SSR drive: 20-28VDC low side open collector switch
SSR, Form A, 0.5A @ 24VAC min., 264VAC max.,
opto-isolated, without contact suppression
Electromechanical relay, Form A, rated 5A, auxiliary output
on PID module, output 2
Electromechanical relay, Form C, rated 5A, auxiliary output
on limit module, output 3
Specifications for Basic Remote User
Interface EZKB (RUI)
Operator Interface
Dual 4 digit, 7 segment LED displays
Forward, backward, up and down keys plus a customer
programmable function key - EZ key
Typical display update rate: 1Hz
Agency approved to IP65/NEMA 4X
Standard bus (ships with all units). Options: EIA 232/485
Modbus
®
RTU, EtherNet/IP™/TCP Modbus
®
or
DeviceNet™, PROFIBUS DP
Line Voltage/Power
100 to 240VAC, +10/-15%; (85-264VAC) 50/60Hz, ±5%
24VAC/VDC, +10/-15%; 50/60Hz, ±5%
Specifications for Mechanical Contactor
Insulation class: UL
®
class B 266°F (130°C)
Min. load of 100 watts
Duty cycle: continuous
40 2 240/277 240 50 120 2
480 200 50 240 3
600 160 50
Full Load Number Line Locked Resistive Amp Max. Horsepower
Amperes of Poles Voltage Rotor Amps Rating Voltage Single-Phase
Contact Ratings
Vista de pagina 1