Specifications
Line Voltage/Power
• 100 to 240VAC, +10/-15%; (85-264VAC), 50/60Hz, ±5%
• 24VAC/VDC, +10/-15%; 50/60Hz, ±5%
• 12VA max. power consumption without mechanical
contactor in system
• 50VA max. power consumption with mechanical
contactor used in system, 140VA if using external
contactor
• Data retention upon power failure via nonvolatile memory
Environment
• 0 to 149°F (-18 to 70°C) operating temperature
• -40 to 185°F (-40 to 85°C) storage temperature
• 0 to 90% RH, non-condensing
Accuracy
• Calibration accuracy and sensor conformity: ±0.1%
of span, ±1°C @ the calibrated ambient temperature and
rated line voltage
• Types R, S, B: 0.2%
• Type T below -50°C: 0.2%
• Calibration ambient temperature @ 77°F ±5°F (25°C ±3°C)
• Accuracy span: 1000°F (540°C) min.
• Temperature stability: ±0.1°F/°F (±0.1°C/°C) rise in
ambient max.
Agency Approvals
• UL
®
, CSA, CE, IP65/NEMA 4X indoor use RUI, RoHS,
W.E.E.E.
• Limit version features FM approval
Controller
• Microprocessor based user-selectable control modes
• PID module: single universal input, 2 outputs
• Limit module: single universal input, 2 outputs
• Two total additional digital input/outputs shared between
PID and limit functions
• Control sampling rates: input = 10Hz, outputs = 10Hz
• Isolated EIA 485 Modbus
®
RTU serial communications
Wiring Termination—Touch Safe Terminals
• Input, power and controller output terminals touch safe
removable 12 to 22 AWG
• Power load terminals 6 to 12 AWG
• Tightening torque: 30 in.-lbs
Universal Input
• Thermocouple, grounded or ungrounded sensors
• >20MΩ input impedance
• Max. of 20Ω source resistance
• RTD 2- or 3-wire, platinum, 100Ω and 1000Ω @ 0°C
calibration to DIN curve (0.00385Ω/Ω/°C)
• Process, 0-20mA @ 100Ω, or 0-10VDC @ 20kΩ input
impedance; scalable, 0-50mV
• Inverse scaling
Digital Input
• Update rate: 1Hz
• Dry contact or dc voltage
DC voltage
• Max. input: 36V at 3mA
• Min. high state: 3V at 0.25mA
• Max. low state: 2V
Dry contact
• Max. short circuit: 13mA
• Min. open resistance: 500Ω
• Max. closed resistance: 100Ω
Current Measurement
• Accuracy: typical ±1A, max. error ±3A
• Accuracy and operating range: 0 to 75A
Digital Output
• Update rate: 1Hz
• Output voltage: 24V, current limit 10mA
Allowable Operating Range
Type J: 32 to 1500°F or 0 to 815°C
Type K: -328 to 2500°F or -200 to 1370°C
Type T: -328 to 750°F or -200 to 400°C
Type N: 32 to 2372°F or 0 to 1300°C
Type E: -328 to 1470°F or -200 to 800°C
Type C: 32 to 4200°F or 0 to 2315°C
Type D: 32 to 4200°F or 0 to 2315°C
Type F: 32 to 2543°F or 0 to 1395°C
Type R: 32 to 3200°F or 0 to 1760°C
Type S: 32 to 3200°F or 0 to 1760°C
Type B: 32 to 3300°F or 0 to 1816°C
RTD (DIN): -328 to 1472°F or -200 to 800°C
Process: -1999 to 9999 units
Output Hardware
• User selectable for heat/cool as on-off, P, PI, PD, PID, or
alarm action. Not valid for limit controls
• Electromechanical relay. Form A, rated 2A
• SSR drive: 20-28VDC low side open collector switch
• SSR, Form A, 0.5A @ 24VAC min., 264VAC max.,
opto-isolated, without contact suppression
• Electromechanical relay, Form A, rated 5A, auxiliary output
on PID module, output 2
• Electromechanical relay, Form C, rated 5A, auxiliary output
on limit module, output 3
Specifications for Basic Remote User
Interface EZKB (RUI)
Operator Interface
• Dual 4 digit, 7 segment LED displays
• Forward, backward, up and down keys plus a customer
programmable function key - EZ key
• Typical display update rate: 1Hz
• Agency approved to IP65/NEMA 4X
• Standard bus (ships with all units). Options: EIA 232/485
Modbus
®
RTU, EtherNet/IP™/TCP Modbus
®
or
DeviceNet™, PROFIBUS DP
Line Voltage/Power
• 100 to 240VAC, +10/-15%; (85-264VAC) 50/60Hz, ±5%
• 24VAC/VDC, +10/-15%; 50/60Hz, ±5%
Specifications for Mechanical Contactor
• Insulation class: UL
®
class B 266°F (130°C)
• Min. load of 100 watts
• Duty cycle: continuous
40 2 240/277 240 50 120 2
480 200 50 240 3
600 160 50
Full Load Number Line Locked Resistive Amp Max. Horsepower
Amperes of Poles Voltage Rotor Amps Rating Voltage Single-Phase
Contact Ratings