12 Watlow Silver Series OIT Installation Guide
Maintenance
Figure 5: DIP switch connections
SW1 SW2 SW3 SW4 Mode
ON OFF OFF OFF Touch Screen Calibration mode
OFF ON OFF OFF Reserved
OFF OFF ON OFF Force into Boot Loader mode
OFF OFF OFF ON Reserved
OFF OFF OFF OFF Normal operation
- Touch Screen Calibration mode: This mode allows you to
recalibrate the touch screen. You also have the option of
restoring the system passwords to defaults (Caution: all project
data in the OIT will be erased if passwords are reset).
- Boot Loader mode: This mode forces the OIT to not execute
the project. This mode is used when replacing or reinstalling the
operating system. Contact Watlow for more information.
- Normal Operation: All DIP switches must be in the OFF
position for normal operation.
Fusing Requirements
If the display does not come on within two seconds of power up, remove
power. An internal fuse will prevent damage if the polarity of the DC
power is incorrect. Check wiring to insure proper connections and try to
power up again.
0600-0069-0000 Rev B