MLS300 Specications
Operator Interface
32-character vacuum fluorescent display
Eight-key keypad to access guided menus and prompts,
enter passkey sequence, set values, switch between single
channel and multiple channel displays
Controller’s configuration can be loaded through the
standard serial port
Analog Inputs
MLS316 16 Differential
MLS332 32 Differential
Noise Rejection
120dB at 60Hz
Temperature Coefficient
40 ppm/°C
Temperature Sensors
Thermocouples: User selectable type, direct connection,
linearization, reference junction compensation, reversed
and shorted T/C detection and upscale break protection
with output averaging.
RTD: 2 or 3 wire, platinum, 100 @ 0°C,
DIN 0.003850//°C curve, user-selectable range.
Two user-selectable ranges offer different resolutions.
Requires special inputs. See Ordering Information.
Input Range and Accuracy
Sensor Range (°C) Range (°F) Accuracy
Type B 66 to 1760°C 150 to 3200°F ±4.0°C
Type E -200 to 787°C -328 to 1448°F ±1.0°C
Type J -212 to 760°C -350 to 1400°F ±1.2°C
Type K -268 to 1371°C -450 to 2500°F ±1.3°C
Type R -18 to 1766°C 0 to 3210°F ±2.8°C
Type S -18 to 1760°C 0 to 3200°F ±2.8°C
Type T -268 to 399°C -450 to 750°F ±1.6°C
RTD1 -100.0 to 275°C -148.0 to 527.0°F ±1.1°C
RTD2 -120 to 840°C -184 to 1544°F ±1.6°C
Note: Accuracy @ 25°C (77°F) ambient. Valid for 10 to 100
percent of span except Type B, which is specified for 427°C
(800°F) to 1760°C (3200°F). RTD is for 100 percent of span.
Linear Voltage and Current Inputs
Requires special inputs. See Ordering Information.
0-10mAÎ(dc)
0-20mAÎ(dc)/4-20mAÎ(dc)
0-100mVÎ(dc)
0-500mVÎ(dc)
0-1VÎ(dc)
0-5VÎ(dc)
0-10VÎ(dc)
0-12VÎ(dc)
Other ranges available. Consult factory.
Pulse Input
One TTL-level square wave input up to 2kHz
Input Sampling Rate @ 60Hz
Each channel has the following scans per second:
MLS316: 1.5 samples per second, (update time: 0.667 sec.)
MLS332: 0.75 samples per second, (update time: 1.33 sec.)
Internal Measurement Resolution
0.006 percent, greater than 14 bits
Calibration
Automatic zero and full scale
Digital Inputs
TTL level used for selecting recipes or jobs, or R/S triggers
Eight inputs and one pulse input with 50-pin terminal board
option
Digital Outputs
34 outputs available with 50-pin terminal board option
One or two control outputs are user assigned for each loop
Each control output can be configured for on-off, time
proportioning or distributed zero crossing
Outputs sink up to 60mA each at 5VÎ(dc)
Alarm Outputs
Independent process and deviation alarms for each channel
Alarms can operate any output not used for control
Programmable deadband, delay and startup suppression
Global alarm output activates when any alarm occurs
Watchdog output indicates controller is functioning correctly
Serial Interface
EIA/TIA-232 or EIA/TIA-485
Baud Rate
2400, 9600 or 19200, user-selectable
Communication Protocol
Modbus
RTU
Line Voltage/Power
15 to 24VÎ(dc) ± 3VÎ(dc) @ 1A
Agency Approvals
UL
®
, C-UL
®
Listed: UL
®
916, Standard for Energy
Management Equipment
CE Mark: Electromagnetic Compatibility (EMC) Directive
89/336/EEC
Firmware Options
Choose firmware with the features needed for the applica-
tion:
Standard—includes closed-loop PID control, auto-tune,
alarms, job memory and failed sensor detection.
Extruder— includes the standard firmware features, with
PID control specifically adapted for plastic extruders.
Ramp and Soak—includes the standard firmware features
with the addition of ramp and soak and process variable
retransmit. Each channel can be configured for standard
PID control or ramp and soak operation. Unused control
outputs on any channel can be configured for retransmit.
Enhanced Features— includes the standard firmware
features with the addition of process variable retransmit,
remote analog setpoint, cascade control, ratio control
and differential control algorithms. Each channel can be
configured for standard PID control or one of the other
control algorithms. Each channel of cascade control or
remote analog setpoint requires two controller channels.
Unused control outputs on any channel can be configured
for retransmit.
Because the MLS300 has no onboard analog outputs,
applications that use process variable retransmit typically
require one SDAC module per retransmitted signal.
Input Module Options
Choose the input module appropriate for the application:
AIM316 and AIM332 provides screw terminations for
16 or 32 sensors
CIM316 and CIM332 provides DB-50 connector
terminations for 16 or 32 sensors in a compact size
Modbus
is a registered trademark of AEG Schneider Automation.